Installing/mounting
4.5 Installing the optional modules
4.5.7

EMC filter modules 6DR4004-6F and -8F

Function
You will require the EMC filter module if you use an external position sensor on the positioner,
e.g. a potentiometer or a non-contacting sensor. The EMC filter module forms the interface
between external position sensors and the basic electronics of the positioner. This module
protects the positioner from electromagnetic effects.
Device features
Figure 4-20
● EMC protection
● Connection to basic electronics
● Connection terminals for:
– External potentiometers with 3 kΩ, 5 kΩ or 10 kΩ
– Signals 0 to 20 mA
– Signals 0 to 10 V
Requirement
● You are familiar with the general procedure described in the section "General information on
installing option modules (Page 53)".
● You have at least one of the following modules:
– 6DR4004-8F EMC filter module / Analog Input Module (AIM) - nEx
– 6DR4004-6F EMC filter module / Analog Input Module (AIM) - Ex
74
Switch block 1
Switch block 2
EMC filter module, schematic diagram
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC