Siemens SIPART PS2 Operating Instructions Manual page 355

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

1. Strip off 85 mm of the cable jacket (with the shielding) and 5 mm of the insulated conductor
insulation of the cable
2. Remove the enclosure cover of the positioner 6DR5910-..., by loosening the four mounting
screws.
3. Insert the prepared cable
4. Tighten the cable gland
5. Connect the conductors of the cable
connection diagram
6. Fasten the enclosure cover with the four mounting screws.
7. Assign a maximum of five positioner (-channels) to the male connector Burndy B50
field distributor
Connecting multiple positioners (Page 356)
8. Plug the male connector Burndy B50
module
9. Specify the number of channels for each PROFIBUS line and set the coding bridges on the
PA module accordingly.
Connecting 19" slide-in modules (Page 358)
PA cable connection for bus connection (Page 357)
Result
The remote electronics in the 19" slide-in module is connected to the positioner 6DR5910-...
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
.
through the cable entry of the positioner.
.
.
.
.
Positioner with remote control electronics
to the terminals
of the positioner according to the
into the Burndy B50
F.2 19" slide-in module
in the
socket on the QRL
355