Commissioning Of Ncs; Prerequisites / Default Settings; B.2.4 Commissioning Of Ncs - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

External position detection
B.2 Non-Contacting Sensor
Procedure
The NCS sensor is equipped with a shielded four-pole cable. Wire this cable to the positioner
as follows:
1. Feed the four-pole NCS cable
of cable gland depends on the positioner version.
2. Tighten the cable gland
3. Terminate the four-pole NCS cable
with the wiring diagram.
4. Place the cable clamp
5. Use the screw
terminal of the positioner.
6. Grounding:
The rear steel panel of the NCS sensor is inevitably bonded to the ground potential of the
system when mounting on the console. This ground connection is only functional if there is
a low-impedance connection to ground potential of the system. Ensure this state by
measuring the ground resistance. If necessary, ensure proper grounding by means of an
additional cable from the NCS sensor to ground potential.
B.2.4

Commissioning of NCS

B.2.4.1

Prerequisites / default settings

1. Supply electrical and pneumatic auxiliary power to the positioner. The top row of the display
shows the current sensor voltage (0 to 100%), while the "NOINI" info flashes in the bottom
row. The pneumatic actuator does not move.
2. If the positioner has already been initialized, perform a reset. Carry out the reset of
parameter group "Init" in the '48.PRST' Preset (Page 158) parameter.
3. Preset for part-turn actuators:
While the valve or flaps are closed, align the North pole of the magnet with the cable; "N" in
position
fiber reinforced polyester (left figure) or anodized aluminum (right figure) (Page 312)".
4. Monitor the display of the positioner while adjusting the actuator to its mechanical stops by
means of
range from P2.0 to P98.0.
Note
This condition cannot be met with slipping flaps or linear actuators that exceed the
mechanical actuation limits.
320
.
onto the outer insulation of the four-pole NCS cable
to bond the cable shielding lug
in "Figure B-4 Mounting on part-turn actuator with magnet holder made of glass
and
at the positioner. Verify that the displayed values never exceed the
through the union nut and the cable gland. Note: The type
in the EMC module of the positioner in accordance
and the cable clamp
Operating Instructions, 05/2019, A5E00127926-AC
.
to the ground
SIPART PS2 with PROFIBUS PA

Advertisement

Table of Contents
loading

Table of Contents