Option Modules; Alarm Module - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Technical data

13.10 Option modules

13.10
Option modules
13.10.1

Alarm module

Alarm module
3 binary output circuits
● Alarm output A1: Terminals 41 and 42
● Alarm output A2: Terminals 51 and 52
● Fault message output: Terminals 31 and 32
● Auxiliary voltage U
Aux
● Signal status
High (not addressed)
Low *) (addressed)
*) The status is also Low if the
basic device is faulty or without
a auxiliary power.
● For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
1 binary input circuit
● Binary input BI2: Terminals 11 and 12, terminals 21 and 22 (jumper)
● Galvanically connected with the
basic device
Signal status 0
Signal status 1
Contact load
● Electrically isolated from the basic
device
Signal status 0
Signal status 1
Internal resistance
290
Without explosion protec‐
tion or suitable for use in
the SIPART PS2 Ex d
6DR4004-8A
≤ 35 V and the current con‐
sumption is to be limited to
< 25 mA
Conductive, R = 1 kΩ,
+3/-1 % *)
Deactivated, I
< 60 µA
R
*) When using in the flame‐
proof housing, the current
consumption must be re‐
stricted to 10 mA per out‐
put.
-
-
-
With Ex protection Ex "ia"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching threshold for
supply according to
EN 60947-5-6:
U
= 8.2 V, R
= 1 kΩ
Aux
i
U
= 15 V DC
i
I
= 25 mA
i
P
= 64 mW
i
C
= 5.2 nF
i
L
= negligibly small
i
Floating contact, open
Floating contact, closed
3 V, 5 μA
≤ 4.5 V or open
≥ 13 V
≥ 25 kΩ
Operating Instructions, 05/2019, A5E00127926-AC
With explosion protection
Ex "ic", "ec", "t"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching threshold for
supply according to
EN 60947-5-6:
U
= 8.2 V, R
= 1 kΩ
Aux
i
"ic":
U
= 15 V DC
i
I
= 25 mA
i
"ec"/"t":
U
≤ 15 V DC
n
C
= 5.2 nF
i
L
= negligibly small
i
SIPART PS2 with PROFIBUS PA