Diagnostics and troubleshooting
12.3 Online diagnostics
See also
Overview of initialization parameters 1 to 5 (Page 134)
Overview of application parameters 6 to 55 (Page 135)
12.3.3

XDIAG parameter

You can use the extended diagnostics parameters to display error messages in one, two or
three stages. In addition to the fault message output, alarm outputs 1 and 2 are then used. For
this purpose, set the "XDIAG" parameter as described in the following table:
Settings of XDIAG
OFF
On1
On2
On3
Possible settings of the 'XDIAG' parameter
12.3.4

Meaning of error codes

12.3.4.1

1 Remaining control deviation

The deviation between the setpoint and the actual value is continuously monitored in
"Automatic" mode. The fault message for a remaining control deviation is activated depending
on the setting of the application parameters " TIM" - monitoring time for setting the fault
messages - and " LIM" - response threshold for the fault message. The fault message is
cancelled as soon as the control deviation drops below the response threshold. This monitoring
function is always active.
12.3.4.2

2 Device not in "Automatic" mode

When the device is not in automatic mode, an error message is generated if the ' FCT'
parameter (function of fault message output) is set correctly. A warning is then sent to the
control system if the device was switched to manual or configuration mode on-site.
12.3.4.3

3 Binary input BIN1 or BIN2 active

If the binary input is activated, an error message is generated when the " FCT" parameter
(function of fault message output) and the "BIN1" parameter (function of binary input 1) are set
correctly. For example, it can be a switch to monitor the packing glands, a temperature switch
or a limit switch (e.g. for pressure).
Binary input 2 (in the optional alarm module) can be configured in a similar manner.
274
Message due to
Extended diagnostics not activated
Fault message output for threshold 3 error message (maintenance alarm, single-stage)
Fault message output for threshold 3 error messages and alarm output 2 for threshold 2
error messages (maintenance demanded, two-stage)
Fault message output for threshold 3 error messages and alarm output 2 for threshold 2
error messages and alarm output 1 for threshold 1 error messages (maintenance required,
three-stage)
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC