Diagnostics and troubleshooting
12.2 Diagnostics
12.2.4.15

Diagnostic value '17.STIC - Stiction (slipstick)'

Requirement:
Display range:
Purpose:
12.2.4.16

Diagnostic value '18.ZERO - Lower endstop'

Requirement:
Display range:
Purpose:
12.2.4.17

Diagnostic value '19.OPEN - Upper endstop'

Requirement:
Display range:
Purpose:
264
Monitoring of stiction (slipstick) 'd.\\STIC' (Page 173) parameter is
activated.
0.0 ... 100.0
This diagnostics parameter shows the filtered value of the slip
jumps in percent resulting from the stiction.
'50.XDIAG' Activation of extended diagnostics (Page 160) param‐
eter is activated.
' 36.YCLS' Tight closing/fast closing with manipulated variable
(Page 150) Parameter is set to one of the following values: 'do', 'uP
do', 'Fd', 'Fu Fd', 'uP Fd', 'Fu do'
0.0 ... 100.0
Indication of how many percent the lower endstop has changed
compared to its value during initialization.
'50.XDIAG' Activation of extended diagnostics (Page 160) param‐
eter is activated.
' 36.YCLS' Tight closing/fast closing with manipulated variable
(Page 150) parameter is set to one of the following values: 'uP',
'uP do', 'Fu', 'Fu Fd', 'uP Fd', 'Fu do'
0.0 ... 100.0
An indication of the current shift of the upper endstop compared to
its initialization value.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC

Advertisement