Cleaning Of The Screens; Positioners 6Dr5..0, 6Dr5..3 And 6Dr5..5 - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Service and maintenance

11.2 Cleaning of the screens

Electrostatic charge
Risk of explosion in hazardous areas if electrostatic charges develop, for example, when
cleaning plastic surfaces with a dry cloth.
● Prevent electrostatic charging in hazardous areas.
11.2
Cleaning of the screens
The positioner is maintenance-free to a large extent. Screens are installed in the pneumatic
connections of the positioners to protect them from rough dirt particles. If there are dirt particles
in the pneumatic auxiliary power supply, they damage the screens and hamper the function of
the positioner. Clean the screens as described in the following two chapters.
11.2.1

Positioners 6DR5..0, 6DR5..3 and 6DR5..5

Procedure for removal and cleaning of the screens
1. Disconnect the pneumatic auxiliary power supply.
2. Remove the pneumatic pipelines.
3. Unscrew the cover of the 6DR5..0 or 6DR5..3 enclosure.
4. Unscrew the three screws on the pneumatic terminal strip.
5. Remove the screens and O-rings behind the terminal strip.
6. Clean the screens, e.g. using compressed air.
Procedure for installation of the screens
Damage to the polycarbonate enclosure 6DR5..0
● The enclosure is damaged due to screwing in the self-tapping screws improperly.
● Ensure that the available thread pitches are used.
● Turn the screws anticlockwise until they engage noticeably in the thread pitch.
● Tighten the self-tapping screws only after they have engaged.
1. Insert the screens into the recesses of the enclosure.
2. Place the O-rings on the screens.
3. Insert the pneumatic terminal strip.
242
WARNING
CAUTION
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC

Advertisement

Table of Contents
loading

Table of Contents