Monitoring the upper limit temperature 'J.\\TMAX'

J. TMAX - Monitoring the upper limit temperature
Requirement:
Possible settings:
180
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 1.
The positioner triggers a threshold 1 message if the current tem‐
perature inside the enclosure undershoots threshold 1. This mes‐
sage is only output if threshold 2 or 3 is not exceeded at the same
time. The process to activate and display this message is described
in the 'XDIAG' parameter.
-25.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 2.
The positioner triggers a threshold 2 message if the current tem‐
perature inside the enclosure undershoots threshold 2. This mes‐
sage is only output if threshold 3 is not exceeded at the same time.
The process to activate and display this message is described in the
'XDIAG' parameter.
-30.0C
-40.0C ... 90.0C
-40.0F ... 194.0F
Use this sub-parameter to set the temperature for threshold 3.
The positioner triggers a threshold 3 message if the current tem‐
perature inside the enclosure undershoots threshold 3. The proc‐
ess to activate and display this message is described in the 'XDIAG'
parameter.
-40.0C
The '50.XDIAG' Activation of extended diagnostics (Page 160) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
● OFF
● On