Siemens SIPART PS2 Operating Instructions Manual page 169

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Factory setting:
b2.LIMIT - Limit
Adjustment range:
Purpose:
Factory setting:
b3.FACT1 - Factor 1
Adjustment range:
Purpose:
Factory setting:
b4.FACT2 - Factor 2
Adjustment range:
Purpose:
Factory setting:
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC
If the time constant is inadequate, the setting of 'b1.TIM' can be
changed manually. Set the time constant in a range from '1' to '400'.
In this case:
● Setting '1' indicates a very weak attenuation.
● Setting '400' indicates a strong attenuation.
The currently determined deviation is displayed in Diagnostics val‐
ue '15.DEVI - Dynamic control valve behavior' (Page 263). The
positioner triggers a message if the current value exceeds one of
the three parameterizable thresholds.
Auto
0.1 ... 100.0
Use this sub-parameter to set a base limit in percent. The base limit
defines the magnitude of the permissible deviation from the expec‐
ted position course. The limit serves as a reference variable for the
fault message factors.
Set the base limit in a range from '0.1' to '100.0'.
1.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'b2.LIMIT' and 'b3.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. This message is only output if threshold 2 or 3 is not exceeded
at the same time. The process to activate and display this message
is described in the 'XDIAG' parameter.
5.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold 1.
Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of 'b2.LIMIT' and 'b4.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. This message is only output if threshold 3 is not exceeded at
the same time. The process to activate and display this message is
described in the 'XDIAG' parameter.
10.0
Parameter assignment
8.3 Description of parameters
169

Advertisement

Table of Contents
loading

Table of Contents