'47.\\Strk' Limit Monitoring For The Number Of Total Strokes; 48.Prst' Preset - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
8.3 Description of parameters
8.3.2.19

'47.\\STRK' Limit monitoring for the number of total strokes

Possible settings:
Purpose:
Description:
Factory setting:
See also
Monitoring of number of total strokes 'L.\\STRK' (Page 182)
'50.XDIAG' Activation of extended diagnostics (Page 160)
Diagnostic value '1.STRKS - Number of total strokes' (Page 259)
8.3.2.20

'48.PRST' Preset

Possible settings:
Purpose:
158
0 ... 1.00E9
Use this parameter to set a limit for the number of total strokes. This
parameter corresponds to the profile parameter 'TO‐
TAL_VALVE_TRAVEL_LIMIT' and was applied for compatibility rea‐
sons.
If the configured limit is exceeded, the 'CB_TOT_VALVE_TRAV' bit
is set in the profile parameter 'CHECK_BACK'.
This function enables preventive maintenance of the control valve.
1E9
● ALL
● Init
● PArA
● diAg
Use this parameter to restore the factory settings for most parame‐
ters. The following parameter groups are available:
● ALL: Reset all parameters together which can be reset by 'Init',
'PArA' and 'diAg'.
● Init: Reset initialization parameters '1.YFCT' to '5.INITM'.
● PArA: Reset parameters '6.SDIR' to '47. STRK' and '51.FSTY'
Safety position (Page 161) to '53.FSVL' Safety setpoint
(Page 162).
● diAg: Reset parameters A to P of the extended diagnostics
function as well as parameter '50.XDIAG'.
An overview of the parameters and factory settings can be found in
section Tabular overview of the parameters (Page 134).
In order to select one of the parameter groups listed above, repeat‐
edly press the
button until the desired setting is output in the
display. Start the function by keeping the
'oCAY' is output in the display. The values of the parameter group
are now the factory settings.
button pressed until
SIPART PS2 with PROFIBUS PA
Operating Instructions, 05/2019, A5E00127926-AC

Advertisement

Table of Contents
loading