Overview Of Advanced Diagnostics Parameters A To P - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
8.2 Tabular overview of the parameters
Parameter
Function
49.PNEUM
Pneumatics type
Standard pneumatic block
Fail in place pneumatic block
Operation with boosters
50.XDIAG
Activation of extended diagnostics
Off
Single stage message
Two stage message
Three stage message
51.FSTY
Safety position
Parameterized safety setpoint
Last setpoint
Open vent valve
52.FSTI
Monitoring period for setting the safety setting
53.FSVL
Safety setpoint
54.STNR
Station number
55.IDENT
Device operating mode (ID No.)
Vendor-independent profile ID number
Device-spec. ID number for full function‐
ality
Automatic adaptation by the control sys‐
tem
1)
2)
3)
4)
8.2.3

Overview of advanced diagnostics parameters A to P

Introduction
These parameters are used to set the extended diagnostics functions of the positioner.
Note
Factory setting
Factory-set parameter values are printed in bold in the following table.
138
Setpoint turning points only appear when '9.SFCT = FrEE' is selected.
'Normally closed' means: Operation when a switch is open or Low level
'Normally open' means: Action on switch closed or High level
'Normal' means: High level, no fault message
'Inverted' means: Low level, no fault message
'+' means: Logical OR combination
Parameter values
Std
FIP
booSt
OFF
On1
On2
On3
FSVL
FSSP
FSAC
0 ... 100
0.0 ... 100.0
0 ... 126
9710
8079
AdAPT
Operating Instructions, 05/2019, A5E00127926-AC
Unit
s
%
SIPART PS2 with PROFIBUS PA