Siemens SIPART PS2 Operating Instructions Manual page 136

Electropneumatic positioner with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
8.2 Tabular overview of the parameters
Parameter
Function
9.SFCT
Setpoint function
Linear
Equal percentage
Inverse equal percentage
Freely adjustable
10.SL0 ...
Setpoint turning point
30.SL20
1)
10.SL0
At
0 %
11.SL1 ....
5 % ...
29.SL19
95 %
30.SL20
100 %
31.DEBA
Deadband of closed-loop controller
32.YA
Start of manipulated variable limit
33.YE
End of the manipulated variable limit
34.YNRM
Standardization of manipulated variable
To mechanical travel
To flow
35.YDIR
Direction of action of manipulated variable for display and position feedback
Rising
Falling
36.YCLS
Tight closing/fast closing with manipulated variable
None
Tight closing Up
Tight closing Down
Tight closing Up and Down
Fast closing Up
Fast closing Down
Fast closing Up and Down
Tight closing Up and fast closing Down
Fast closing Up and tight closing Down
37.YCDO
Value for fast closing/tight closing Down
38.YCUP
Value for fast closing/tight closing Up
136
Parameter values
1 : 25
1 : 33
1 : 50
25 : 1
33 : 1
50 : 1
Operating Instructions, 05/2019, A5E00127926-AC
Lin
1 - 25
1 - 33
1 - 50
n1 - 25
n1 - 33
n1 - 50
FrEE
0 ... 100.0
Auto / 0.1 ... 10.0
0.0 ... 100.0
0.0 ... 100.0
MPOS
FLoW
riSE
FALL
no
uP
do
uP do
Fu
Fd
Fu Fd
uP Fd
Fu do
0.0 ... 100.0
0.0 ... 100.0
SIPART PS2 with PROFIBUS PA
Unit
%
%
%
%
%
%

Advertisement

Table of Contents
loading