FAQ / TROUBLESHOOTING
6

Valve is opening instead of closing or vice versa...

Change direction in programming Parameter #7 to RISE or FALL to
whichever is required.
7
If power is interrupted and the connection between the PS2 is
broken...
The PS2 Positioner will vent all gas inside the actuator on the single
acting Positioner.
A double acting PS2 Positioner will vent what ever is up stream of port
Y2 and supply full regulator set pressure to Y1, closing or opening the
valve.
When power is restored and you have 4-20 mA, the unit will power up
and go directly into the Automatic Mode. There is no need for
reprogramming the PS2 Positioner.
8
Positioner goes past 0% or past the closed to a negative value...
Sign of over travel. This could be due to worn trim.
Improper calibration - re-calibrate.
9
Valve doesn't fully open or close...
Check to see gearing has not been changed either in the Program
parameters or on the physical selection switch.
Check connections for loose hardware. This causes dead band.
Check for proper air supply pressure.
Improper calibration - re-calibrate.
Valve is plugged with material.

10 Valve actuates too quickly...

Set restrictor valve to slow down pneumatically (Refer to Figure 17).
Set ramp up and ramp down time accordingly, in the programming
parameter numbers 10 and 11.
* Consult the Programming parameter chart on Pages 31 & 32 to choose time
increments accordingly.