FAQ / TROUBLESHOOTING
6
Valve is opening instead of closing or vice versa...
Change direction in programming Parameter #7 to RISE or FALL to
•
whichever is required.
7
If power is interrupted and the connection between the PS2 is
broken...
The PS2 Positioner will vent all gas inside the actuator on the single
•
acting Positioner.
A double acting PS2 Positioner will vent what ever is up stream of port
•
Y2 and supply full regulator set pressure to Y1, closing or opening the
valve.
When power is restored and you have 4-20 mA, the unit will power up
•
and go directly into the Automatic Mode. There is no need for
reprogramming the PS2 Positioner.
8
Positioner goes past 0% or past the closed to a negative value...
Sign of over travel. This could be due to worn trim.
•
Improper calibration - re-calibrate.
•
9
Valve doesn't fully open or close...
Check to see gearing has not been changed either in the Program
•
parameters or on the physical selection switch.
Check connections for loose hardware. This causes dead band.
•
Check for proper air supply pressure.
•
Improper calibration - re-calibrate.
•
Valve is plugged with material.
•
10 Valve actuates too quickly...
Set restrictor valve to slow down pneumatically (Refer to Figure 17).
•
Set ramp up and ramp down time accordingly, in the programming
•
parameter numbers 10 and 11.
* Consult the Programming parameter chart on Pages 31 & 32 to choose time
increments accordingly.