POSITIONER SET UP &
Positioner Set Up (Continued)

13 Auto-calibrate:

a
While still in Programming Mode, scroll to Parameter 4.
b
Hold the '+' Key down for 5 seconds.
c
This initializes the Auto Calibration program, which sets up your VALVE
AND ACTUATOR CURVE automatically.
d
There are 5 run sequences, they switch systematically without the need
for intervention. A chattering sound is normal.
e
When the Auto-Calibration stops, the screen will indicate FINSH, at this
time you can push the 'HAND' Key once (quickly, do not hold down), this
will take you back to the program Parameters reading # 4.
f
Hold down on the 'HAND' Key for 5 Seconds, this will store
everything to Memory and will take you back into Manual Mode.
14 Press the 'HAND' Key and this returns the positioner into the AUTO Mode,
which will then respond to your controller's output signal (or the mA source
you have connected). Stroke the valve with your mA source to ensure linearity
(e.g. check valve stroke at 0%, 25%, 50% etc.).
15 Fine-tuning and customizing of programming can be further accomplished,
please consult the SIPART PS2 Operation Instructions for the instructions and
procedures on (programming/customizing) your positioner for each application.

Clearing the memory

To restore the positioner to factory "out of box" default settings refer to Parameter
50. PRST (Pages 25 & 26) for reset options (option 'ALL' will completely reset the
positioner to factory default settings).
1
In Programming Mode, scroll to parameter 50.
2
Use the '-' & '+' Keys to scroll to the reset option required. Reset
options are listed on Page 30.
3
Press and hold the '+' Key on the desired reset option, the word Strt
will be displayed for several seconds.
4
When cleared the word oCay will be displayed. Let go of '+' Key.
5
The selected parameters will now have been reset to factory defaults.
Dyna-Flo Control Valve Services Ltd.
Phone: 780
469
CALIBRATION
4000 | Toll Free: 1
866
396
2356 | www.dynafl o.com