York YLAA Series Installation Operation & Maintenance page 52

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4-10 fan, 55 - 230 ton, 195 - 700 kw
Table of Contents

Advertisement

SECTION 5 – TECHNICAL DATA
TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS (CONT'D)
CHILLER
VOLTAGE
MODEL
CODE
125
136
142
155
156
170
175
200
230
52
MIN CKT.
AMPS
208
512
230
511
380
309
460
258
575
204
208
579
230
577
380
338
460
285
575
226
208
579
230
577
380
338
460
285
575
226
208
618
230
617
380
374
460
311
575
246
208
634
230
632
380
383
460
319
575
252
208
740
230
738
380
447
460
372
575
295
208
740
230
738
380
447
460
372
575
295
208
734
230
731
380
443
460
369
575
292
208
959
230
956
380
599
460
504
575
359
MIN DUAL
MIN N/F
ELEM
DISC SW
FUSE &
MIN CB
800
600
800
600
400
350
400
300
250
225
800
600
800
600
600
400
400
300
400
250
800
600
800
600
600
400
400
300
400
250
800
700
800
700
600
400
400
350
400
300
800
700
800
700
600
400
400
350
400
300
1000
800
1000
800
600
500
600
400
400
350
1000
800
1000
800
600
500
600
400
400
350
1000
800
1000
800
600
500
600
400
400
300
1200
1000
1200
1000
600
600
600
600
600
400
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
MAX DUAL
ELEM
FUSE
MAX CB
600
600
350
300
225
600
600
400
300
250
600
600
400
300
250
700
700
400
350
300
700
700
400
350
300
800
800
500
400
350
800
800
500
400
350
800
800
500
400
300
1000
1000
600
600
400
JOHNSON CONTROLS

Advertisement

Table of Contents
loading

Table of Contents