FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
LIFTING USING LUGS
Units are provided with lifting holes in the base frame
which accept the accessory lifting lug set as shown in
the figure below. The lugs (RH and LH) should be in-
serted into the respective holes in the base frame and
turned so that the spring loaded pin engages into the
hole and the flanges on the lug lock behind the hole.
The lugs should be attached to the cables/chains using
shackles or safety hooks.
CORRECT
LIFTING HOLE
LUG
IN BASE FRAME
FLANGE
LOCKING PIN
LUG
LOCKING
PIN
JOHNSON CONTROLS
INCORRECT
LUG
FLANGE
LOCKING PIN
LIFTING HOLE
IN BASE FRAME
FLANGE
SECTION 3 – HANDLING AND STORAGE
LIFTING USING SHACKLES
The shackles should be inserted into the respective
holes in the base frame and secured from the inside.
Use spreader bars to avoid lifting chains hitting the
chiller. Various methods of spreader bar arrangements
may be used, keeping in mind the intent is to keep the
unit stable and to keep the chains from hitting the chill-
er and causing damage.
Lifting Instructions are placed on a label on the chiller
and on the shipping bag.
3
33