Leaving Chilled Liquid Control Override To Reduce Cycling; Figure 39 - Setpoint Adjust; Table 19 - Sample Compressor Staging For Return Water Control; Table 20 - Return Chilled Liquid Control For 4 Compressors (6 Steps) - York YLAA Series Installation Operation & Maintenance

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4-10 fan, 55 - 230 ton, 195 - 700 kw
Table of Contents

Advertisement

FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017

TABLE 19 - SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL

# OF COMP ON
45 °F
RWT
(7.2 °C)
*Unloading only
LEAVING CHILLED LIQUID CONTROL
OVERRIDE TO REDUCE CYCLING
To avoid compressor cycling the microprocessor will
adjust the setpoint upward temporarily. The last run
time of the system will be saved. If the last run time
was greater than 5 minutes, no action is to be taken.
If the last run time for the lead system was less than 5
minutes, the microprocessor will increase the setpoint
high limit according to the chart at right, with a maxi-
mum value allowed of 50 °F (see Figure 29 on page
152).
If adding the setpoint adjust value to the setpoint high
limit causes the setpoint high limit to be greater than 50
°F, the setpoint high limit will be set to 50 °F, and the
difference will be added to the setpoint low limit.
Once a system runs for greater than 5 minutes, the set-
point adjust will be set back to 0. This will occur while
the system is still running.

TABLE 20 - RETURN CHILLED LIQUID CONTROL FOR 4 COMPRESSORS (6 STEPS)

*STEP
COMPRESSOR
0
1
2
3
4
5
6
NOTES:
1. Step 1 is Hot Gas Bypass and is skipped when loading occurs. Hot Gas Bypass operation is inhibited during Pumpdown.
2. Step 3 is skipped when loading occurs.
3. Step 4 is skipped when unloading occurs.
* STEP can be viewed using the OPER DATA key and scrolling to COOLING DEMAND.
JOHNSON CONTROLS
COMPRESSOR STAGING FOR RETURN WATER CONTROL
4 COMPRESSOR
COOLING SETPOINT = 45 °F (7.2 °C) RANGE = 10 °F (5.6 °C)
0
* 1+HG
46.25 °F
(7.9 °C)
COMPRESSOR ON POINT
0
1 W/HGB
1 NO HGB
2
2
3
4
1
2
47.5 °F
50.0 °F
(8.6 °C)
(10.0 °C)
6
5
4
3
2
1
0
0
1
2
LAST RUN TIME OF LEAD SYSTEM (MINUTES)

FIGURE 39 - SETPOINT ADJUST

SETPOINT
SP + CR/8 (Note 1)
SP + CR/4
SP + 2*CR/4 (Note 2)
SP + 2*CR/4
SP + 3*CR/4
SP + CR
SECTION 8 – UNIT OPERATION
3
4
52.5 °F
55.0 °F
(11.4 °C)
(12.8 °C)
3
4
5
LD11415
COMPRESSOR OFF POINT
SETPOINT
SETPOINT
SP + CR/8
SP + CR/4
SP + CR/4 (Note 3)
SP + 2*CR/4
SP + 3*CR/4