SECTION 7 – UNIT CONTROLS
S Y S
X
S U C T
S A T
S U C T
Displays the System Suction Temp and Saturated Suc-
tion Temp when an EEV is installed.
S Y S
X
L L S V
H O T
G A S
Displays whether the System Liquid Line Solenoid or
Hot Gas Solenoid was energized at the time of the fault.
S Y S
X
F A N
Displays the number of Fan Stages in the system active
at the time of the fault.
S Y S
X
A C T U A L
= X X X . X
Displays the system Amperage (calculated approxi-
mately) at the time of the fault.
For this message to appear, CURRENT FEEDBACK
ONE PER SYSTEM must be programmed under the
OPTIONS key. If the microprocessor is programmed
as one CURRENT FEEDBACK ONE PER UNIT un-
122
=
X X X . X ° F
=
X X X . X ° F
I S
X X X
S O L
I S
X X X
S T A G E
X X X
A M P S
A M P S
der the PROGRAM key, the display will be the first
display prior to the SYS 1 info. If the microprocessor is
programmed for CURRENT FEEDBACK NONE, no
current display will appear.
Displays for System 1 starting with SYS X NUMBER
OF COMPS RUNNING X through SYS X AMPS =
XXX.X VOLTS = X.X will be displayed first, fol-
lowed by displays for System 2.
Further explanation of the above displays is cov-
ered under the STATUS, OPER DATA, COOLING
SETPOINTS, PROGRAM, and OPTIONS keys.
Software Version
The software version may be viewed by first pressing
the HISTORY key and then repeatedly pressing the ↓
(DOWN) arrow key until you scroll past the first his-
tory buffer choice.
D I S P L A Y
S A F E T Y
D O W N
N O . 1
After the ↓ (DOWN) arrow key is pressed again, the
software version will appear.
C O N T R O L
I / O
FORM 150.72-ICOM6
ISSUE DATE: 12/29/2017
S H U T -
( 1 T O 6 )
C. M X X. Z Z. Y Y
C. M X X. 1 8. Y Y
JOHNSON CONTROLS