Status Registers; A.2 Status Registers - Vaisala HMD60 Series User Manual

Humidity and temperature transmitters for ducts in hvac
Hide thumbs Also See for HMD60 Series:
Table of Contents

Advertisement

Integer Values (x100, Non-metric)
392
0187
1)
NOTE: 16-bit integers have a maximum value of +32767. Certain measurement parameters
(for example, mixing ratio and enthalpy) can exceed this value in x100 scaling. In such cases,
the value of the parameter is cut off at +32767, and measurements above this value are not
reported. Verify that the measurement ranges in your application are suitable for the 16-bit
integer format with x100 scaling; whenever possible, it is recommended to use 32-bit float
values.
A.2 Status Registers
Table 13 Modbus Status Data Registers (Read-Only)
Register
Address
Number
(Hexade
(Decima
cimal)
l)
513
0200
hex
514
0201
hex
0202
hex
516
0203
hex
0204
hex
1)
Enthalpy
hex
Register Description
Device status
Error code
Security hash
16-bit signed
integer
Data Format
16-bit signed integer 0000
32-bit signed
integer
32-bit signed
integer
Appendix A – Modbus Registers
Btu/lb
Bitmask
:Status OK
hex
0001
: Critical error,
hex
maintenance needed.
0002
: Error, device may
hex
recover automatically
0004
: Warning
hex
0008
: Notification
hex
0010
: Calibration mode
hex
active
0201
(status code low): see
hex
Table 14 (page 52)
0202
(status code high): see
hex
Table 15 (page 52)
Security hash changes on any
change to device settings/
adjustments.
51