Summary of Contents for Immergas VICTRIX ZEUS SUPERIOR 26 2 ERP

  • Page 1 VICTRIX ZEUS Instruction and recommendation booklet SUPERIOR 26 2 - 32 2 ERP...
  • Page 3 Read the following pages carefully: you will be able to draw useful suggestions regarding the correct use of the appliance, the respect of which, will confirm your satisfaction for the Immergas product.
  • Page 4: Table Of Contents

    ......29 probe (Optional)......... 8 system pressure.........26 3.8 Programming the P.C.B......30 1.9 Immergas flue systems....... 9 2.10 System drainage........26 3.9 "Chimney sweep function" ......32 1.10 Tables of resistance factors 2.11 Storage tank draining.......26 3.10 Pump anti-block function.
  • Page 5: Boiler Installation

    The place of installation of the appliance and Failure to comply with the above implies personal relative Immergas accessories must have suitable responsibility and invalidates the warranty. features (technical and structural) such to allow •...
  • Page 6: Main Dimensions

    2 (EN 1717:2002). The materials used for the central heating circuit of Immergas boilers withstand ethylene and propylene glycol based antifreeze liquids (if the mixtures are prepared perfectly). For life and possible disposal, follow the sup- plier's instructions.
  • Page 7: Gas Connection

    The gas supply pipe must be suitably ply respecting L-N polarity and earth connection; dimensioned according to current regulations Attention: Immergas declines all liability in the , this network must also have a multi-pole cir- in order to guarantee correct gas flow rate to the event of damage caused by the inclusion of auto- cuit breaker with class III over-voltage category.
  • Page 8: Remote Controls And Room Chrono-Thermostats (Optional)

    All Immergas chrono-thermostats are connected precision and therefore with evident saving probe. The probe can be connected directly to with 2 wires only. Carefully read the user and in running costs.
  • Page 9: Immergas Flue Systems

    • Coupling extension pipes and concentric Attention: the boiler must be installed ex- elbows. To install push-fitting extensions with clusively with an original Immergas “Green other elements of the flue, proceed as follows: Range” inspectionable air intake device and Install the concentric pipe or elbow with the...
  • Page 10 Equivalent Resistance Equivalent Equivalent length Equivalent length length in m TYPE OF DUCT Factor length in metres in metres of pipe in m of concentric of concentric pipe of pipe Ø 80 Ø 60 pipe Ø 80/125 Ø 60/100 Intake m 7.3 Concentric pipe Ø...
  • Page 11: Outdoor Installation In A

    (B ) or ducted directly outside via a vertical terminal for direct exhaust (B or via an Immergas ducting system (B The technical regulations in force must be respected. • Coverage kit assembly (Fig. 1-11). Remove the cap and gasket from the intake hole.
  • Page 12: Concentric Horizontal Kit Installation

    Make sure that the external silicone wall concentric bend leaving the boiler. If addi- Immergas also provides a Ø 60/100 simplified sealing plate is properly inserted in the wall. tional components are assembled, the length terminal, which in combination with its exten- N.B.: for proper system operation the terminal...
  • Page 13: Concentric Vertical Kit Installation

    1.13 CONCENTRIC VERTICAL KIT male side (5) (smooth) into the flange (2) up to Position the fixed half-shell (5) on the aluminium INSTALLATION. the end stop; making sure that the wall sealing tile and insert the intake-exhaust pipe (7). Fit the Type C configuration, sealed chamber and plate has been fitted (3), this will ensure sealing 80/125 Ø...
  • Page 14: Separator Kit Installation

    1.14 SEPARATOR KIT INSTALLATION. side (smooth) to the female side of the bend Type C configuration, sealed chamber and (5) up to the end stop; making sure that the fan assisted. internal wall sealing plate has been fitted, this will ensure sealing and joining of the elements Separator kit Ø...
  • Page 15: Adaptor C9 Kit Installation

    N.B.: to encourage the removal of possible - The maximum vertical extension using a Ø 60 This kit allows an Immergas boiler to be installed condensate forming in the exhaust pipe, tilt ducting system is 13 m, the maximum exten- in "C...
  • Page 16: Ducting Of Flues Or Technical Slots

    Immergas ducting system. The Ø 60 rigid and Ø Ø 80 exhaust terminal, 1m of Ø 80 pipe in ex- relevant terminal, unless otherwise provided 80 flexible “Green Range”...
  • Page 17: Flues, Chimneys, Chimney Pots And Terminals

    1.19 FLUES, CHIMNEYS, CHIMNEY POTS 1.22 GAS SYSTEM START-UP. AND TERMINALS. To start up the system, refer to the technical The flues, chimneys and chimney pots for the standard in force. evacuation of combustion products must be in In particular, for new gas systems: compliance with applicable standards.
  • Page 18: Circulation Pump

    Furthermore, within the parameter it is pos- 2 ErP). sible to adjust the operation range of the circulator setting limit speed (adjustable from 83 % for model Victrix Zeus Superior 26 2 ErP Head available to the system. 1-28 Victrix Zeus Superior 26 2 ErP...
  • Page 19: Kits Available On Request

    The boiler is prepared for of the pump kit. Immergas supplies a series of empty just the boiler without having to empty application of the polyphosphate dispenser kit.
  • Page 20: Use And Maintenance Instructions

    USE AND MAINTENANCE ensure that a qualified technician checks the ef- not be disposed of like normal household waste ficiency of the ducting or other devices. nor abandoned in the environment, but must be INSTRUCTIONS Never clean the appliance or connected parts removed by a professionally qualified firm.
  • Page 21: Description Of Functioning States

    DESCRIPTION OF FUNCTIONING means of the indicator (6) with a brief descrip- STATES tion. Refer to the instruction book for a complete Below find a list of boiler functioning states that explanation. appear on the multifunction display (24) by Display (6) Description of functioning states Summer functioning mode without request in progress.
  • Page 22: Using The Boiler

    2.5 USING THE BOILER. • Functioning with external probe (Fig. 2-6) Adjustment of the system flow temperature optional. In the case of a system with optional Before ignition make sure the central heating sys- tem is filled with water and that the manometer external probe, the boiler flow temperature (23) indicates a pressure of 1 - 1.2 bar;...
  • Page 23: Troubleshooting

    2.6 TROUBLESHOOTING. to the following example (e.g. CAR = Exx, Super The Victrix Zeus Superior ErP boiler signals CAR = ERR>xx). any anomalies by the flashing symbol (5) along with the “ERRxx” indication on the indicator (6) where “xx” corresponds to the error code described in the following table.
  • Page 24 Error Anomaly signalled Cause Boiler status / Solution Code If the board detects an anomaly on the flue gas probe the boiler will not Flue probe anomaly start Power cycle the boiler. If the Remote Con- trol is still not detected on re-starting the boiler will switch to local operating mode, Loss of remote This occurs in the event of connection to a non compatible remote control...
  • Page 25: Parameters And Information Menu

    2.7 PARAMETERS AND INFORMATION - “M3” customisations By turning the central heating temperature se- MENU. lector switch (3) scroll through the menu items. - “M5” configurations: menu reserved to the By pressing the button "D" it is possible to access By pressing button “D”...
  • Page 26: Boiler Shutdown

    1 and 1.2 bar. If the pressure falls below 1 bar (with the circuit of the Immergas Anti-freeze Kit in the boiler. In cold) restore normal pressure via the valve located the case of prolonged inactivity (second case), we also recommend that: at the bottom of the boiler (Fig.
  • Page 27: Boiler Start-Up (Initial Check)

    BOILER START-UP (INI- and central heating modes; - check ventilation and/or aeration of the instal- lation room where provided. TIAL CHECK) - check the CO in the fumes at maximum and minimum flow rate; If even only a single safety check offers a negative To commission the boiler: result, do not commission the system.
  • Page 28: Wiring Diagram

    3.2 WIRING DIAGRAM. 1     BK - Black Key: 4     BL - Blue A4 - Display board BR - Brown B1 - Flow probe 5     G - Green B2 - Domestic hot water probe 3     2     GY - Grey B4 - External probe (optional) G/Y - Green-Yellow B5 - Return probe OR - Orange...
  • Page 29: Calibration Of Number Of Fan Revs

    (about 30 sec.). pressure points (18 and 20 Fig. 1-29). Attention: the CO verification operations must Victrix Zeus Superior 26 2 ErP Access the configurations menu under the “SER- be carried out with the casing mounted, while the at nominal at minimum VICE"...
  • Page 30: Programming The P.c.b

    3.8 PROGRAMMING THE P.C.B. By pressing the button "D" it is possible to access Listed below are the items in the“M5” menu The boiler is prepared for possible programming the main menu, divided into three main parts: with default parameters and possible options of several operation parameters.
  • Page 31 M5 menu (password must be entered) Value Default 1st Level 2nd Level Options Description value by the tech- nician With the external probe present it defines at which minimum external temperature the boiler must operate at the maximum flow temperature (see P66/C graph Fig.
  • Page 32: Chimney Sweep Function

    M5 menu (password must be entered) Value Default 1st Level 2nd Level Options Description set by the value technician RELE3-0 Relay 3 not used Check the storage tank recirculation pump RELE3-1 (not used on this model) The relay signals the intervention of boiler block ( Can be coupled to an RELE3-2 external signalling device, not supplied) The relay signals that the boiler is on and in the heating stage...
  • Page 33: Appliance Check And Maintenance

    3.16 APPLIANCE CHECK AND - Check the operation of the appliance control MAINTENANCE. and adjustment devices and in particular: The following checks and maintenance should - intervention of the main electrical switch on be performed at least once a year. the boiler;...
  • Page 34: Casing Removal

    3.17 CASING REMOVAL. - Unscrew the 2 (6) fastening screws of the casing To facilitate boiler maintenance the casing can front (7) and release it by pushing it up. be completely removed by following these simple - Loosen the screws (8) in the lower part of the instructions (Fig.
  • Page 35: Variable Heat Output

    15°C. Victrix Zeus Superior 26 2 ErP. METHANE (G20) BUTANE (G30) PROPANE (G31)
  • Page 36: Combustion Parameters

    3.19 COMBUSTION PARAMETERS. Supply pressure mbar (mm H 20 (204) 29 (296) 37 (377) Victrix Zeus Superior 26 2 ErP Gas nozzle diameter 5.70 4.10 4.10 Flue flow rate at nominal heat output kg/h Flue flow rate at min heat output kg/h at Q.
  • Page 37: Technical Data

    3.20 TECHNICAL DATA. Victrix Zeus Superior 26 2 Victrix Zeus Superior 32 2 Domestic hot water nominal heat input kW (kcal/h) 26,9 (23137) 33.0 (28392) Central heating nominal heat input kW (kcal/h) 21,7 (18678) 33.0 (28392) Minimum heat input kW (kcal/h) 5,0 (4323) 7.3 (6279) Domestic hot water nominal heat output (useful)
  • Page 38: Key For Data Nameplate

    3.21 KEY FOR DATA NAMEPLATE. Cod. Md Sr N° Cod. PIN Type n min. max. n min. n max. Class CONDENSING N.B.: the technical data is provided on the data plate on the boiler Model Cod. Md Model code Sr N° Serial Number Check Cod.
  • Page 39: Technical Parameters For Mixed Boilers (In Compliance With Regulation 813/2013)

    Contact information IMMERGAS S.p.A. VIA CISA LIGURE, 95 - 42041 BRESCELLO (RE) ITALY (*) High temperature mode means 60°C on return and 80°C on flow. (**) Low temperature mode for condensation Boilers means 30°C , for low temperature boilers 37°C and for other appliances 50°C of return tempera- ture.
  • Page 40: Product Data Sheet (In Compliance With Regulation 811/2013)

    3.23 PRODUCT DATA SHEET (IN COMPLIANCE WITH REGULATION 811/2013). Victrix Zeus Superior 26 2 ErP Victrix Zeus Superior 32 2 ErP VICTRIX ZEUS SUPERIOR 26 2 ErP VICTRIX ZEUS SUPERIOR 32 2 ErP Parameter value Parameter value Yearly energy consumption for the heating Yearly energy consumption for the heating 40.3 GJ...
  • Page 41: Parameters For Filling

    3.24 PARAMETERS FOR FILLING IN THE to make up the assembly (e.g. solar devices, in- ASSEMBLY SHEET. tegration heat pumps, temperature controllers). In case you should wish to install an assembly, Use sheet fig. 3-8 for “assemblies” related to starting from the Victrix Zeus Superior ErP the heating function (e.g.: boiler + temperature boiler (26 2 or 32 2), use the assembly charts in controller).
  • Page 42 Parameters for filling in assembly chart. Parameter Victrix Zeus superior 26 2 ErP Victrix Zeus superior 32 2 ErP ‘I’ ‘II’ ‘III’ 1,27 0.84 ‘IV’ 0,50 0.33 * to be established by means of table 5 of Regulation 811/2013 in case of “assembly” including a heat pump to integrate the boiler.
  • Page 43 Facsimile for filling in domestic hot water production system assembly chart. Water heating energy efficiency of combination heater ‘I’ Declared load profile: Solar contribution From fiche of solar device Auxiliary electricity ( 1,1 ‘I’ 10 % ) ‘II’ ‘III’ ‘I’ Water heating energy efficiency of package under average climate Water heating energy efficiency class of package under average climate <...
  • Page 44 Parameters for filling in DHW package assembly chart. Parameter Victrix Zeus superior 26 2 ErP Victrix Zeus superior 32 2 ErP ‘I’ ‘II’ ‘III’ * to be determined according to Regulation 811/2013 and transient calculation methods as per Notice of the European Community no. 207/2014.
  • Page 48 Follow us Immergas Italia immergas.com Immergas S.p.A. 42041 Brescello (RE) - Italy Tel. 0522.689011 Fax 0522.680617 Certified company ISO 9001...