(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1
COMPR. #2
RLA
LRA
RLA
LRA
55.8
425
55.8
425
55.8
425
55.8
425
36.0
239
36.0
239
26.9
187
26.9
187
23.7
148
23.7
148
76.9
505
76.9
505
71.2
505
71.2
505
41.1
280
41.1
280
33.9
225
33.9
225
27.1
180
27.1
180
JOHNSON CONTROLS
ELECTRICAL DATA (ENGLISH) (CONT'D)
YCAL0019_ – YCAL0066_
Single-Point Field Supplied Power Wiring (See Figure 12)
Disconnect Switch (optional) or Circuit Breaker (optional)).
FANS
COMPR. #1
QTY
FLA
RLA
RLA
2
7.6
44.0
55.8
2
7.4
19.1
55.8
2
4.5
23.1
36.0
2
4.0
19.0
26.9
2
2.9
15.3
23.7
2
7.6
30.9
59.9
2
7.4
37.0
55.5
2
4.5
22.3
32.0
2
3.4
17.2
26.4
2
2.9
14.6
21.1
SYSTEM #2 COMPRESSOR & FAN
COMPR. #2
LRA
RLA
LRA
QTY
425
55.8
425
2
425
55.8
425
2
239
36.0
239
2
187
26.9
187
2
148
23.7
148
2
425
59.9
425
2
425
55.5
425
2
239
32.0
239
2
187
26.4
187
2
148
21.1
148
2
SECTION 5 – TECHNICAL DATA
FANS
FLA
RLA
7.6
44.0
7.4
19.1
4.5
23.1
4.0
19.0
2.9
15.3
7.6
30.9
7.4
37.0
4.5
22.3
3.4
17.2
2.9
14.6
5 5