FORM 150.67-NM1
ISSUE DATE: 4/28/2017
TABLE 1 - TEMPERATURES AND FLOWS
LEAVING WATER
TEMPERATURE ( °F)
YCAL
MINIMUM
0019
40
0022
40
0028
40
0033
40
0043
40
0046
40
0052
40
0056
40
0066
40
Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special
care should be taken when multiple chillers are fed by a single pump.
NOTES:
1. For leaving brine temperature below 40 °F (4.4 °C), contact your nearest Johnson Controls Office for application requirements.
2. For leaving water temperature higher than 55 °F (12.8 °C), contact the nearest Johnson Controls Office for application guidelines.
3. The evaporator is protected against freezing to -20 °F (-28.8 °C) with an electric heater as standard.
4. For operation at temperatures below 25 °F (-3.9 °C), the optional Low Ambient Kit will need to be installed on the system
(for YCAL0043 to YCAL0065).
5. For operation at temperatures above 115 °F (46.1 °C), the optional High Ambient Kit will need to be installed on the system.
Voltage Limitations
The following voltage limitations are absolute and operation beyond these limitations may cause serious damage
to the compressor.
TABLE 2 - VOLTAGE LIMITATIONS
UNIT POWER
200-3-60
230-3-60
380-3-60
460-3-60
575-3-60
JOHNSON CONTROLS
SECTION 5 – TECHNICAL DATA
OPERATIONAL LIMITATIONS (ENGLISH)
MAXIMUM
MINIMUM
55
55
55
55
55
55
55
55
55
MINIMUM
ENGLISH
COOLER FLOW (GPM)
MAXIMUM
17
68
21
84
30
150
34
150
40
200
40
200
40
300
60
300
60
300
180
207
355
414
517
AIR ON CONDENSER ( °F)
MINIMUM
MAXIMUM
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
MAXIMUM
220
253
415
506
633
5 5
47