Figure 10 - Single-Point Supply Connection - Terminal Block, Non-Fused Disconnect Switch Or Circuit Breaker - York YCAL0019 Installation, Operation And Maintenance Manual

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

SECTION 4 – INSTALLATION
SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED
DISCONNECT SWITCH OR CIRCUIT BREAKER
Power Panel
Power Panel
Power Panel
Terminal Block,
Terminal Block,
NF Disconnect SW
NF Disconnect SW
or Circuit Breaker
or Circuit Breaker
Electrical Notes and Legend located on Page 59.
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or
death, the technician should verify
that NO LETHAL VOLTAGES are
present inside the panel AFTER dis-
connecting power, PRIOR to working
on equipment.
FIGURE 10 - SINGLE-POINT SUPPLY CONNECTION – TERMINAL BLOCK, NON-FUSED DISCONNECT
SWITCH OR CIRCUIT BREAKER (0043 – 0066)
44
1L1 1L2 1L3
1L1 1L2 1L3
1L1 1L2 1L3
See electrical note 9
See electrical note 9
Control Panel
Control Panel
Control Panel
2
2
2
L
L
L
MICROPANEL
MICROPANEL
CTB2
CTB2
CTB2
13
13
13
CTB1
CTB1
Field Provided 120-1-60
Field Provided 120-1-60
Micropanel Power Supply if Control
Micropanel Power Supply if Control
Transformer not Supplied
Transformer not Supplied
Field Provided Unit Power Supply
Field Provided Unit Power Supply
The unit evaporator heater uses
120VAC. Disconnecting 120VAC pow-
er from the unit, at or below freezing
temperatures, can result in damage to
the evaporator and unit as a result of
the chilled liquid freezing.
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
Flow Switch
Flow Switch
14
14
14
LD07719
JOHNSON CONTROLS

Hide quick links: