Table 39 - Values Required For Bas Communication; Table 40 - Real Time Error Numbers - York YCAL0019 Installation, Operation And Maintenance Manual

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

SECTION 10 – MAINTENANCE

TABLE 39 - VALUES REQUIRED FOR BAS COMMUNICATION

SETTING DESCRIPTION
DE MODIFIER ADDRESS
DE MODIFIER OFFSET
P1 PROTOCOL
P1 MANUAL MAC ADDRESS
P1 BAUD RATE
P1 PARITY
P1 STOP BITS
P2 PROTOCOL
P2 MANUAL MAC ADDRESS
P2 BAUD RATE
P2 PARITY
P2 STOP BITS
P2 HW SELECT BIT
RESET REAL TIME ERROR
P1 HW SELECT BIT
CHILLER ID
as Required By Network
1
or Other As Required By Network
2
number Is Multiplied By 100, Set As Required By Network
3
number Is Added To De Modifier Address, Set As Required By Network
4
unit Operating Software Version C.Mmc.13.03 Or Later Required For Modbus Protocol
5
Reboot required (cycle power) after
settings are changed.
218
BACNET MS/TP
0 TO 41943
0 TO 99
BACNET
0-127
(1)
9600 To 76800 or Auto Selectable
NONE
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A

TABLE 40 - REAL TIME ERROR NUMBERS

ERROR NUMBER
(##)
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
PROTOCOL
MODBUS RTU
(3)
(4)
(1)
MODBUS SVR
0-127
19,200
NONE
RS-485 OR RS-232
The table below shows the real time error numbers that
may be encountered during communication setup and
a description of each.
DESCRIPTION
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
YORKTALK 2
5
1
0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
(1)
N/A
(2)
N/A
(2)
1
N/A
N/A
(1)
N/A
N/A
N/A
N/A
N/A
JOHNSON CONTROLS
-1
0