Table 35 - Entering/Leaving Chilled Liquid Temperature Sensor; Liquid And Refrigerant Sensor Test Points - York YCAL0019 Installation, Operation And Maintenance Manual

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

SECTION 9 – SERVICE AND TROUBLESHOOTING
TABLE 35 - ENTERING/LEAVING CHILLED LIQ-
UID TEMPERATURE SENSOR
VOLTAGE
TEMP °F
(SIGNAL INPUT
TO RETURN)
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
208
TEMP °C
1.33
-12
1.39
-11
1.46
-10
1.51
-9
1.58
-8
1.65
-7
1.71
-6
1.78
-4
1.85
-3
1.91
-2
1.98
-1
2.05
0
2.12
1
2.19
2
2.26
3
2.33
4
2.40
6
2.47
7
2.53
8
2.60
9
2.65
10
2.73
11
2.80
12
2.86
13
2.92
14
2.98
16
3.05
17
3.11
18
3.17
19
3.23
20
3.29
21
3.34
22
3.39
23
3.45
24
3.5
26
3.54
27

Liquid and Refrigerant Sensor Test Points

(Table 35)
Entering Chilled Liquid Sensor
J6-5 = +5VDC regulated supply to sensor.
J6-8 = VDC input signal to the I/O board. See Table 35
for voltage readings that correspond to specific
liquid temperatures.
J6-2 = Drain (shield connection = 0VDC) Return.
Leaving Chilled Liquid Temperature Sensor
J6-4 = +5VDC regulated supply to sensor.
J6-7 = VDC input signal to the microboard. See Table
35 for voltage readings that correspond to spe-
cific liquid temperatures.
J6-1 =drain (shield connection = 0VDC) Return.
FORM 150.67-NM1