Option 15 – Refrigerant Type - York YCAL0019 Installation, Operation And Maintenance Manual

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

SECTION 7 – UNIT CONTROLS
Option 15 – Refrigerant Type
R E F R I G E R A N T
R – 4 1 0 A
Refrigerant type R-410A must be selected under Ser-
vice Mode. Refrigerant type is displayed under the OP-
TIONS key, but is only programmable in Service Mode.
Incorrect programming may cause
damage to compressors.
Option 16 – Expansion Valve Type
E X P A N S I O N
T H E R M O S T A T I C
Expansion valve type, thermostatic or electronic
may be selected under Service Mode. Expansion valve
type is displayed under the OPTIONS key, but is only
programmable in Service Mode. YCAL 0019 through
YCAL 0066 chillers will typically always be equipped
with thermostatic expansion valves.
Incorrect programming may cause
damage to compressors.
Also see the Unit Keys Programming Quick Reference
List in Table 16.
Option 17 – Flash Card Update
F L A S H
C A R D
D I S A B L E D
A Flash Card is used to input the operating program
into the chiller IPU. A Flash Card is used instead of
an EPROM. Normally, a Flash Card update is not re-
quired and the message above will be displayed.
If the operating software is to be updated, insert the
Flash Card into the Flash Card input port. Turn off the
Unit Switch and set the FLASH CARD UPDATE TO
"ENABLED" using the ↑ and ↓ keys.
180
T Y P E
V A L V E
T Y P E
U P D A T E
F L A S H
C A R D
E N A B L E D
Press the ENTER key and the following message will
be displayed until the update has been completed. The
keypad and display will not respond during the update.
DO NOT reset or power down the chiller until the up-
date is completed.
F L A S H
C A R D
P L E A S E
W A I T . . .
After the update is completed, an automatic reboot will
occur. If an error occurred, the following message will
appear with the error code and no reboot will occur:
F L A S H
C A R D
E R R O R
If the update resulted in an error, the original program
will still be active. When an error occurs, assure the
correct Flash Card was utilized. Incorrect chiller soft-
ware will cause an error. If this is not the case, the
Flash Card is most likely defective or the IPU and I/O
combo board is bad.
Option 18 – Remote Temperature Reset
R E M O T E
T E M P
I N P U T
REMOTE TEMP RESET INPUT selection is pro-
grammable according to the type of input utilized. The
following options are available:
• DISABLED (default)
• 0.0 – 10.0VDC
• 2.0 – 10.0VDC
• 0.0 – 20.0mA
• 4.0 – 20.0mA
The options display message for Re-
mote Temperature Reset Input only
appears if the Temperature Reset Op-
tion is enabled under Service Mode.
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
U P D A T E
U P D A T I N G
U P D A T E
XXXXX
R E S E T
XXXXXXXXXXXXXX
JOHNSON CONTROLS