FORM 150.67-NM1
ISSUE DATE: 4/28/2017
Options Key
There are many user programmable options under the
OPTIONS key. The OPTIONS key is used to scroll
through the list of options by repeatedly pressing the
OPTIONS key. After the selected option has been dis-
played, the ↑ (UP) and ↓ (DOWN) arrow keys are then
used to change that particular option. After the option
is changed, the ENTER/ADV key must be pressed to
enter the data into memory.
Many of the "Options" displayed are
only programmable under the "Ser-
vice Mode" and not under the OP-
TIONS key. Options only program-
mable under the "Service Mode"are
noted in the details describing the
option.
Table 16 shows the programmable options. Following
are the displays in the order they appear:
Option 1 – Language
D I S P L A Y
E N G L I S H
English, Spanish, French, German, and Italian can be
programmed.
Option 2 – System Switches: (two system
units only)
(Single System Display is similar)
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This allows both systems to run.
JOHNSON CONTROLS

UNIT KEYS

OPTIONS
CLOCK
L A N G U A G E
O N
O N
or
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns system 2 OFF.
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns system 1 OFF.
or
S Y S
1
S W I T C H
S Y S
2
S W I T C H
This turns systems 1 and 2 OFF.
Turning a system OFF with its system
switch allows a pumpdown to be per-
formed prior to shutdown.
Option 3 – Chilled Liquid Cooling Type:
C H I L L E D
W A T E R
The chilled liquid is water. The Cooling Setpoint can be
programmed from 40 °F to 70 °F (4.4 °C to 21.1 °C).
or
C H I L L E D
G L Y C O L
SECTION 7 – UNIT CONTROLS
00070VIP
O N
O F F
O F F
O N
O F F
O F F
L I Q U I D
L I Q U I D
177
7