System Trip Volts - York YCAL0019 Installation, Operation And Maintenance Manual

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

FORM 150.67-NM1
ISSUE DATE: 4/28/2017
N U M B E R
O F
P E R
S Y S T E M
The NUMBER OF FANS PER SYSTEM must be pro-
grammed as needed to match the number of fans on
each system.
S Y S
X
T R I P
U N I T
T R I P
= X . X
Depending on the option, the trip voltage for a
specific system or unit high current trip can be
programmed. It also calibrates the current read-
out under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas.

System Trip Volts

For individual system high current trip programming
on chillers:
• Add the sum of the compressor and fan RLA's in
the system.
• Multiply the sum by 1.25.
• Divide by 225A.
• The resulting voltage is the value that should be
programmed.
JOHNSON CONTROLS
F A N S
= X
V O L T S
= X . X
V O L T S
V O L T S
V O L T S
For example, if fan and compressor RLA's total 100A:
5V x 100A
x 1.25 =
225A
The programmed value will be 2.8V. A similar calcula-
tion and programming will be necessary for the other
system in a 2-system chiller.
Unit Trip Volts
For total chiller high current trip programming on
460VAC chillers:
• Add the sum of all the compressor and fan RLA's
in the chiller.
• Multiply the sum by 1.25.
• Divide by 225A.
• The resulting voltage is the value that should be
programmed.
For example, if fan and compressor RLA's total 180A:
5V x 180A
x 1.25 =
225A
The programmed value will be 5.0V.
R E M O T E
U N I T
P R O G R A M M E D
When communications is required with a BAS or Op-
tiView Panel, individual unit IDs are necessary for
communications with specific chillers on a single RS-
485 line. ID 0-7 is selectable.
SECTION 7 – UNIT CONTROLS
625VA
2.8V
=
225A
1125VA
= 5.0V