York YCAL0019 Installation, Operation And Maintenance Manual page 112

Air-cooled liquid chillers hermetic scroll
Table of Contents

Advertisement

SECTION 5 – TECHNICAL DATA
62 5/8"
61 7/8"
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6'; rear
to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'. No more
than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".
112
DIMENSIONS – YCAL0066 (ENGLISH)
6 3/4"
3 1/4"
VIEW B-B
3 15/16"
BOTTOM OF PANEL
LIQUID OUT
90 1/4" BASE WIDTH
LEFT END
7/8" TYP.
LIQUID IN
ELECTRICAL ACCESS
PANEL
9 15/16"
3" ANSI/AWWA C-606
(typ)
12 5/8"
43 1/8"
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
34 11/16"
15 3/4"
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents