SECTION 5 – TECHNICAL DATA
50 1/16"
2 1/4"
TO ACCESS PANEL 13 3/8"
2" VICTAULIC CONN (TYP)
LIQUID OUT
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6'; rear
to wall – 6'; cooler end to wall – 4'0"; coil end to wall – 6'; top – no obstructions allowed; distance between adjacent units – 10'. No more
than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".
100
DIMENSIONS – YCAL0028 (ENGLISH)
3 1/4"
6 3/4"
3 15/16"
VIEW B-B
BOTTOM OF PANEL
B
49 1/4"
15 1/2"
8 5/16"
44 5/16"
BASE WIDTH
LEFT END
7/8" TYP .
2" VICTAULIC CONN (TYP)
LIQUID IN
B
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
8 1/2"
10 3/4"
8 5/16"
19"
FORM 150.67-NM1
ISSUE DATE: 4/28/2017