5.3.2 User data via PROFIBUS

German
English name Abbreviation
name
Sollwert
Setpoint
Istwert
Readback
Diskrete Pos-
Position dis-
tion
crete
Aktorzustand
Checkback
Fernkaskade
Remote Ca-
Eingang
scade Input
Fernkaskade
Remote Ca-
Ausgang
scade Output
Setpoint
Readback
Position discrete
SIPART PS2 PA Manual
A5E00127926--05
In this example all fies supported by the device are transmitted in the
input or output direction. 256 (W#16#100) is selected as the initial I/O
address.
Byte 15
15 bytes of input data consisting of the following:
READBACK
RCAS_OUT
CHECKBACK 3 Byte
POS_D
Byte 10
10 bytes of output data consisting of the following:
SP
RCAS_IN
The positioner can exchange a combination of the following cyclic
useful data with the PROFIBUS.
SP
RB
POS_D
CB
RCAS_IN
RCAS_OUT
The setpoint consists of a floating--point value (4 bytes and the
associated status (1 byte, see below).
The readback indicates the position of the valve. The readback
consists of a floating--point value (4 bytes) and the associated status (1
byte).
The discrete position of the valve is displayed as a value (1 byte) with
the following meaning:
0 = not initialized
1 = valve closed
2 = valve open
3 = valve in intermediate state
There is a status for this value too (1 byte)
Functions/operation via PROFIBUS PA
5 Byte
5 Byte
2 Byte
5 Byte
5 Byte
Direction
Length in
from the
Byte
point of view
of the posi-
tioner
Input
5
Output
5
Input
2
Input
3
Input
5
Input
5
Consisting of
Value/Status
Value/Status
Value/Status
Value
Value/Status
Value/Status
141