Meaning Of The Diagnostic Values - Siemens 6DR55 Series Manual

Electropneumatic positioner for linear and part--turn actuators
Table of Contents

Advertisement

Operation
No.
Abbrevia--
Meaning
tion
28
T7
Number of operating hours in Temperature range 7
29
T8
Number of operating hours in Temperature range 8
30
T9
Number of operating hours in Temperature range 9
31
VENT1
Number of cycles pre--controlvalve 1
32
VENT2
Number of cycles pre--controlvalve 2
33
STORE
Store current values as "last maintenance"
(press increment key for 5 s) (Store)
34
PRUP
Prediction up
35
PRDP
Prediction down
36
WT00
Number of operating hours in distance class WT00
37
WT05
Number of operating hours in distance class WT05
38
WT10
Number of operating hours in distance class WT10
39
WT30
Number of operating hours in distance class WT30
40
WT50
Number of operating hours in distance class WT50
41
WT70
Number of operating hours in distance class WT70
42
WT90
Number of operating hours in distance class WT90
43
WT95
Number of operating hours in distance class WT95
Table 1
Overview diagnostic values

4.5.2 Meaning of the diagnostic values

1 STRKS
2 CHDIR
3 CNT
114
Number of strokes (total valve travel)
The actuator movements during operation are totaled and can be read
here as number of strokes. Unit: 100% stokes, i.e. the distance
between 0 to 100 % and backwards. The value is written every 15
minutes in a non--volatile memory. It can be reset to zero with the
increment key
.
Number of direction changes
Every change in direction leaving the dead zone is noted in the
controller and added to the number of changes of direction.
The value is written every quarter of an hour in a non--volatile memory.
It can be reset to zero with the increment key
Fault counter
Every fault is noted in the controller and added to the number of fault
messages. The counter can be reset to zero with the increment
key--
.
Displayable
Unit
values
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
--
0 to 4.29E9
--
--
--
1 to 40
--
1 to 40
--
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
0 to 4.29E9
Hours
.
SIPART PS2 PA Manual
A5E00127926--05
Rest
poss.
x
x
x
x
x
x
x
x

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sipart ps2 pa

Table of Contents