7. Set the limits L1 and L2 as described in the chapter "Setting the limits of the slotted
8. An insulating cover is provided over the SIA module. Place the insulating cover on one
9. Place the insulating cover on the SIA module by bending the module covers carefully.
10.Engage the basic electronics into the four brackets.
11.Fix the basic electronics using both the fixing screws.
12.Reestablish all electrical connections between the basic electronics and the option
13.Using both the screws, fasten the module cover provided. Do not use the standard
14.Select the labels that already exist on the standard version of the module cover from the
4.7.4.1
Setting the limits of the slotted initiator alarm unit
Procedure: Determining the switch status of the slotted initiators
You will require a suitable display device to determine the switch status. For example, use
the initiator tester type 2 / Ex from Pepperl + Fuchs.
1. Connect the display device to the following terminals of the SIA module:
2. Read the switch status of slotted initiators.
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
Note
Pin in the actuating disk bearing
A pin
is pressed in the actuating disk bearing
1. Align the pin
before it touches the special screw
2. Rotate the actuating disk bearing
the pin
is inserted into the special screw
initiator alarm unit (Page 59)".
side under the basic electronics seat on the module cover. The recesses of the insulating
cover must fit in the corresponding webs of the module cover.
modules. Connect the basic electronics and the option modules to the ribbon cables
provided. Connect the basic electronics and the potentiometer to the potentiometer cable.
module cover.
label set provided. Affix the selected labels on the installed module cover as per the
standard version.
– 41 and 42
– 51 and 52
.
.
and the special screw
.
Installing/mounting
4.7 Installing option modules
simultaneously so that
59