Siemens SIPART Series Operating Instructions Manual page 54

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents

Advertisement

Installing/mounting
4.7 Installing option modules
4.7.1.2
Installing the optional modules in the "flameproof enclosure" version
Introduction
The following option modules are available for the positioner in the flameproof enclosure:
● I
● Alarm module
● EMC filter module
Risk of explosion
You must fulfill the following conditions before supplying auxiliary power to the positioner in
potentially hazardous areas:
• The installed electronic unit has been approved.
• The enclosure of the positioner is closed.
• The duct openings for electronic connections must be closed. Only use the Ex d certified
• You must install an ignition trap if you use a "conduit piping system". The maximum
52
module
y
DANGER
cable entries or sealing plugs.
distance between the ignition trap and the positioner enclosure is 46 cm or 18".
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sipart ps2 series

Table of Contents