12.8.7.3
Certificates, approvals, explosion protection for all device versions
Electrical data
For connecting to circuits with the
following peak values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in accordance with
Intrinsic safety "ia"
Intrinsic safety "ic"
Non-sparking "nA"
Permissible ambient temperature
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.
Ex markings
ATEX
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC 110°C Db
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +60 °C (-40 ... +140 °F)