Technical data
12.8 Option modules
12.8.2
Iy module
I
module
y
Direct current output for position
feedback
1 current output, terminals 61 and 62
Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
246
Without Ex protection/
with Ex protection Ex d
6DR4004-8J
+12 ... +35 V
-
-
Safe galvanic isolation from alarm option and basic device
With Ex protection Ex ia
(only in temperature class
T4)
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/i [mA]
H
≤ 0.3%
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1%
≤ 1 %
U
= DC 30 V
i
I
= 100 mA
i
P
= 1 W
i
C
= 11 nF
i
L
= negligibly small
i
DC 840 V, 1 s
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6J
+12 ... +30 V
"ic":
U
= DC 30 V
i
I
= 100 mA
i
"nA"/"t":
U
≤ DC 30 V
n
I
≤ 100 mA
n
P
≤ 1 W
n
C
= 11 nF
i
L
= negligibly small
i

Advertisement