Technical data
12.8 Option modules
See also
Basic safety instructions (Page 113)
Pneumatic connection on the standard controller (Page 93)
12.8
Option modules
12.8.1
Alarm module
Alarm module
3 binary output circuits
Alarm output A1: Terminals 41 and 42
Alarm output A2: Terminals 51 and 52
Fault message output: Terminals 31 and 32
Auxiliary voltage U
H
Signal status
High (not addressed)
Low *) (addressed)
*) The status is also Low if the
basic device is faulty or without
a auxiliary power.
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
244
Without Ex protection/
with Ex protection Ex d
6DR4004-8A
≤ 35 V
Conductive, R = 1 kΩ,
+3/-1 % *)
Deactivated, I
< 60 µA
R
*) When using in the
flameproof housing, the
current consumption must
be restricted to 10 mA per
output.
-
-
-
With Ex protection Ex "ia"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
U
= DC 15.5 V
i
I
= 25 mA
i
P
= 64 mW
i
C
= 5.2 nF
i
L
= negligibly small
i
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6A
-
≥ 2.1 mA
≤ 1.2 mA
Switching thresholds for
supply as per EN 60947-
5-6:
U
= 8.2 V, R
= 1 kΩ
H
i
"ic":
U
= DC 15.5 V
i
I
= 25 mA
i
"nA"/"t":
U
≤ DC 15.5 V
n
C
= 5.2 nF
i
L
= negligibly small
i