Technical data
12.1
Rated conditions
Rated conditions
Ambient temperature
Permissible ambient temperature for operation
Degree of protection
1)
Mounting position
Vibration resistance
Harmonic oscillations (sine) according to EN 60068-2-
6/10.2008
Bumping (half-sine) according to EN 60068-2-27/02.2010
Noise (digitally controlled) according to EN 60068-2-
64/04.2009
Recommended range of continuous operation of the entire
control valve
Climate class
Storage
Transport
Operation
2)
Max. impact energy 1 Joule for enclosure with inspection window 6DR5..0 and 6DR5..1.
1)
At ≤ -10 °C (≤ 14 °F), the display refresh rate is limited. In the case of use with I
2)
-20 to +80 °C (-4 to +176 °F) for 6DR55..-0G ..., 6DR56..-0G ..., 6DR55..-0D ... and 6DR56..-0D...
3)
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
In hazardous areas, observe the maximum permissible
ambient temperature corresponding to the temperature
class.
-30 ... +80 °C (-22 ... +176°F)
IP66 to EN 60529/NEMA 4X
Any; in wet environment, pneumatic connections and
outlet opening not upward
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axle
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axle
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axle
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axle
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to DIN EN 60721-3-4
1K5, but -40 ... +80°C (1K5, but -40 ... +176°F)
2K4, but -40 ... +80°C (2K4, but -40 ... +176°F)
4K3, but -30 to +80 °C (4K3, but -22 to +176 °F)
module, only T4 is permissible.
y
12
3)
235