Alarm, error, and system messages
10.4 Fault correction
10.4.6
Remedial measures table 5
Fault profile (symptoms)
Zero point displaces sporadically
(> 3%).
The device function has completely
failed: No representation on the
display either.
Fault table 5
See also
Repair/Upgrading (Page 233)
230
Possible cause(s)
Impact or shock loads result in
accelerations so high that the
friction clutch moves, e.g. due to
"vapor shocks" in vapor lines.
Electrical auxiliary power supply is
not adequate.
In case of very high continuous
loads due to vibrations
(oscillations):
Screws of the electrical connecting
terminals may be loosened.
Electrical connecting terminals
and/or electronic components may
be knocked out.
Remedial measures
Rectify the causes for shock loads.
Re-initialize the position controller.
Check the electrical auxiliary power
supply.
Tighten the screws firmly and
secure using sealing wax.
Repair
For prevention: Install the positioner
on the damping pads.