10.4.5
Remedial measures table 4
Symptoms
In stationary automatic mode
(constant setpoint) and in manual
mode, both piezo valves continually
switch alternately, and the actuator
oscillates around a mean value.
Positioner doesn't move control
valve to the stop (at 20 mA).
Error table 4
See also
Cleaning of the screens (Page 232)
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
Possible cause(s)
Sticking friction of the packing gland
from the control valve or actuator
too large
Looseness (play) in the
positioner/actuator/control valve
system
Actuator too fast
Supply pressure too low. Load on
the feeding controller or system
output is too low.
Alarm, error, and system messages
10.4 Fault correction
Remedial measures
Reduce friction or increase dead
zone of positioner (parameter
"dEbA") until the oscillation stops.
Part-turn actuator: Check for firm
seating of set screw on coupling
wheel.
Linear actuator: Check for firm
seating of lever on positioner shaft.
Correct any other play between the
actuator and the control valve.
Increase actuating times using
throttle screws.
If a quick actuating time is needed,
increase the dead zone (parameter
"dEbA") until the oscillation stops.
Increase supply pressure, insert
ballast converter
Select 3/4-wire mode