Alarm, error, and system messages
10.4 Fault correction
10.4.2
Remedial measures table 1
Fault profile (symptoms)
Positioner remains in "RUN 1".
Positioner remains in "RUN 2".
Positioner remains in "RUN 3".
Positioner remains "RUN 5", does
not go up to "FINISH" (waiting time
> 5 min).
Fault table 1
See also
Cleaning of the screens (Page 232)
Operation with boosters (Page 269)
226
Possible cause(s)
Initialization started from the end
position and
The response time of a maximum of
1 minute was not observed.
Network pressure not connected or
it is too low.
Transmission ratio selector and
parameter 2
"YAGL" and the real stroke do not
match.
Incorrectly set stroke on the lever.
Piezo valve does not activate.
Actuator actuating time is too high.
"Gap" (play) in the positioner -
actuator - control valve system
Remedial measures
A waiting time of up to 1 minute is
essential.
Do not start initialization from the
end position.
Provide the network pressure.
Check settings: see leaflet: "Device
view (7)" picture as well as
parameters 2 and 3
Check the stroke setting on the
lever. See table 2
Open the restrictor completely
and/or set the pressure PZ (1) to
the highest permissible value.
Use a booster if required.
Part-turn actuator: check for the
firmness of the grub screw of the
coupling wheel
Linear actuator: check for the
firmness of the lever on the
positioning shaft.
Remove any play between the
actuator and the control valve.