Alarm, error, and system messages
10.1 Output of system messages in the display
10.1.4
System messages during operation
Remarks on the tables:
nn
/
Messages during operation:
Message
Line
Abov
Below Automatic
e
CPUSTA
X
RT
X
HW /
X
ERROR
NOINI
X
nnn.n
X
AUTnn
X
MANnn
oFL /
X
127.9
EXSTP
X
EX UP
X
206
stands for changeable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Mode
Manual
X
X
X
X
X
X
X
X
Meaning / cause
P-manual
Message after application
of electrical auxiliary
power
Fault in the hardware
X
Positioner is not initialized
Actual position [in %] for
initialized positioner.
Flashing decimal point
shows communication
with a class-2 master
Automatic mode (nn =
setpoint)
Manual mode
(nn = setpoint)
Display range exceeded.
Possible causes:
Friction clutch or
•
transmission ratio
•
selector was disturbed
or
Positioner was
•
installed on a different
actuator without being
reinitialized
Actuator was stopped with
the binary input
Actuator is moved to the
upper stop with binary
input
Operating Instructions, 10/2013, A5E00074631-11
Measure
Maintenance
•
Replace
•
electronics
Start initialization
•
Switch to
•
automatic mode
with mode button
Offset friction
•
clutch so that
when the actuator
moves the actual
value display
stays between 0.0
and 100.0, or
transmission ratio
•
selector, or
perform factory
•
settings (Preset)
and initialization
SIPART PS2 with and without HART