Siemens SIPART Series Operating Instructions Manual page 208

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents

Advertisement

Alarm, error, and system messages
10.1 Output of system messages in the display
10.1.4
System messages during operation
Remarks on the tables:
nn
/
Messages during operation:
Message
Line
Abov
Below Automatic
e
CPUSTA
X
RT
X
HW /
X
ERROR
NOINI
X
nnn.n
X
AUTnn
X
MANnn
oFL /
X
127.9
EXSTP
X
EX UP
X
206
stands for changeable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Mode
Manual
X
X
X
X
X
X
X
X
Meaning / cause
P-manual
Message after application
of electrical auxiliary
power
Fault in the hardware
X
Positioner is not initialized
Actual position [in %] for
initialized positioner.
Flashing decimal point
shows communication
with a class-2 master
Automatic mode (nn =
setpoint)
Manual mode
(nn = setpoint)
Display range exceeded.
Possible causes:
Friction clutch or
transmission ratio
selector was disturbed
or
Positioner was
installed on a different
actuator without being
reinitialized
Actuator was stopped with
the binary input
Actuator is moved to the
upper stop with binary
input
Operating Instructions, 10/2013, A5E00074631-11
Measure
Maintenance
Replace
electronics
Start initialization
Switch to
automatic mode
with mode button
Offset friction
clutch so that
when the actuator
moves the actual
value display
stays between 0.0
and 100.0, or
transmission ratio
selector, or
perform factory
settings (Preset)
and initialization
SIPART PS2 with and without HART