G2.LEVL2 - threshold 2
Use this sub-parameter to set a threshold in percent. Use threshold 2 to monitor the upper
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the upper hard end stop
and the initialization value exceeds threshold 2. The process to activate and display this fault
message is described in the "XDIAG" parameter.
The factory setting is "2.0".
G3.LEVL3 - threshold 3
Use this sub-parameter to set a threshold in percent. Use threshold 3 to monitor the upper
hard end stop. Set the threshold in a range from "0.1" to "10.0".
The positioner triggers a fault message if the difference between the upper hard end stop
and the initialization value exceeds threshold 3. The process to activate and display this fault
message is described in the "XDIAG" parameter.
The factory setting is "4.0".
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
Parameterizing/addressing
9.4 Description of parameters