Siemens SIPART Series Operating Instructions Manual page 184

Electropneumatic positioners with and without hart
Hide thumbs Also See for SIPART Series:
Table of Contents

Advertisement

Parameterizing/addressing
9.4 Description of parameters
C2.FACT1 - factor 1
Use this sub-parameter to set the factor for the formation of limit threshold 1. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C2.FACT1".
The threshold 1 error message is displayed when the limit threshold 1 is exceeded. The
procedure to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.0".
C3.FACT2 - factor 2
Use this sub-parameter to set the factor for the formation of limit threshold 2. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C3.FACT2".
The threshold 2 error message is displayed when the limit threshold 2 is exceeded. The
procedure to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "1.5".
C4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "100.0". The limit threshold is the product of "C1.LIMIT" and
"C4.FACT3".
The threshold 3 error message is displayed when the limit threshold 3 is exceeded. The
procedure to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "2.0".
182
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11