DIP Switch Setup
DIP Switch Setup
Termination and bias guidelines:
 
The last battery in the chain should have termination and bias
l
 
The last meter should have termination, without bias
l
 
Inverter communication board should not have   t ermination if meter is installed, otherwise ON.
l
Verify that the DIP switches of all the devices   a re set as described in the following table, according to the 
components used in the system and their location:
System Component
Inverter communication board
(Figure 15)
Batteries Type B (Figure 16)
Batteries Type C, E (Figure
17)
Meter (Figure 18)
28
SolarEdge StorEdge -Single Battery/High Capacity Installation MAN-01-00283-1.1
Communication and Termination
Switches
Termination:
If a meter is installed: SW7 Down -
o
No termination
If a meter is not installed: SW7 Up -
o
termination ON.
(see also Creating an RS485 Bus
Connection on page 63)
Modbus protocol:
 
Single battery or the battery is the
l
last in the chain:
S2, S6: Left
o
S1, S5: Down
o
S3, S4: UP
o
If the battery is not the last in the
l
chain:
S2, S6: Left
o
S1, S5: Down
o
S3, S4: Down
o
Termination:
If the battery is not the last in the
o
chain: Middle - No termination
Single battery or the battery is the
o
last in the chain: Bottom -
Termination (with bias)
Modbus protocol:
 
Right (RS485)
o
N/A
Address Switches
N/A
Battery address 1 (ID 24) - located
closest to the inverter
Switch 1: Right
o
Switch 2: Right
o
Switch 3: Right
o
Battery address 2 (ID 25)
Switch 1: Left
o
Switch 2: Right
o
Switch 3: Right
o
Battery Address 1 (ID 24) - located
closest to the inverter
Switch 1: Right
o
Switch 2: Right
o
Switch 3: Right
o
Battery Address 2 (ID 25)
Switch 1: Left
o
Switch 2: Right
o
Switch 3: Right
o
Meter 1 address:
Switch 1: Up
o
Other: Down
o
Meter 2 address:
Switch 2: Up
o
Other: Down
o