Fuse Replacement

Fuse Replacement
Replacement kits are available from SolarEdge or you can use other fuses with identical ratings.
 1. Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe 
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
 2. Turn OFF the StorEdge Connection Unit and the AC switch of the distribution panel.
 3. Open and remove the StorEdge Connection Unit cover.
 4. Open and remove the internal transparent cover.
 5. Remove the faulty fuse from the upper board of the StorEdge Connection Unit and replace with a 
new fuse.
 6. Close the StorEdge Connection Unit covers.

StorEdge Connection Unit Replacement

Removing the Existing StorEdge Connection Unit

 1. Turn OFF the inverter ON/OFF switch, and wait until the LCD indicates that the DC voltage is safe 
(<50V), or wait five minutes before continuing to the next step.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five
minutes for the input capacitors of the inverter to discharge.
 2. Turn OFF the StorEdge Connection Unit and the AC switch of the distribution panel.
 3. Disconnect the DC and battery cables from the StorEdge Connection Unit.
 4. Open the inverter cover.
100
SolarEdge StorEdge -Single Battery/High Capacity Installation MAN-01-00283-1.1
Figure 47: StorEdge Connection Unit fuses