Wiring; 2-Wire Connection, With Terminals 6 Through 10 - Siemens SIPART PS2 Service Manual

Smart valve positioner 4/20 ma
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Wiring

4.1

2-Wire Connection, with terminals 6 through 10

Non-hazardous area
Hazardous area
Basic electronics
✓ Requires a regulated current source NOT a voltage source
✓ Unit requires at least 3.6 milliamps to power on
✓ Do NOT use the 24 volt pair of wires for the feedback card on terminals 6 and 8 (if
equipped)
✓ For hazardous areas, consult Power Specifications (Page 44) and local safety guidelines
Connect positive wire for 4 to 20 mA to terminal 6, negative wire to terminal 8.
PS2 Troubleshooting Guide
Service Manual, 03/2017, A5E36661550-AA
Binary input 1
Signal source
HART communicator
4
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents