Troubleshooting Procedures

3.30 Valve Does Not Go Fully Closed/Open

3.30
Valve Does Not Go Fully Closed/Open
● From AUT or MAN mode, press
– Observer parameter name in the lower left hand corner.
● Continue to press
– Note: While in configuration mode, the positioner is NOT controlling the valve.
● Use
● To exit configuration mode, press and hold
– Unit should be in Manual Mode.
● Press and release
● Verify the valve assembly goes to the fully open and/or closed position with a 0 or 100%
command signal.
● If not:
– The problem may be the input signal. Use the PS2's display as a current meter. This
– Verify unit is in Automatic mode.
– Provide a 4 mA input signal.
– Press all three buttons down until display changes.
● Press the
– While pressing and holding
● Go to option "mA".
● Observe display and verify if the positioner is actually displaying ≈ 4 mA. If not, then the
input signal is the cause.
● To exit diagnostic mode, press and hold
42
button until "YCLS" Parameter is reached.
and
buttons to change Parameter values:
Set Parameter YCLS to "Up do" (Tight Closing Up and Down
button once to enter AUTO mode.
is found in Diagnostic parameter "mA".
○ Diagnostic menu will be displayed. The diagnostic name can be found in the lower
right corner.
button to advance through the menu.
button for 5 seconds.
button for 5 seconds.
button, press the
button to go backwards in menu.
button for 5 seconds.
Service Manual, 03/2017, A5E36661550-AA
)
PS2 Troubleshooting Guide