5.2.3

Connecting NCS to EMC filter module

Requirements
You need the EMC filter module with article number C73451-A430-D23 to connect the NCS
to the positioner. The positioner supplies auxiliary power to the NCS via the EMC filter
module.
Wiring diagram
Figure 5-20
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Positioner (open state)
Vcc: Yellow
Vref: Green
Vpos: Black
Ground: Brown
EMC filter module C73451-A430-D23
Example of connecting the NCS to the EMC filter module
Cable clamp
Screw F3x8
Cable gland
Four-pole NCS cable
Non Contacting Sensor (NCS)
Cable shielding lug
Connection