Installing/mounting
4.7 Installing option modules
The alarm module has the following features:
● Available in two versions.
– Explosion-proof version for connecting to a switching amplifier in conformity with
– Non-explosion-proof version for connecting to power sources having a maximum of
● Three binary outputs. Binary inputs are potentially separated from the basic configuration
and from each other.
● The binary input BIN2 has two inputs. Both inputs are implemented as logical OR
combination.
– Input 1 at terminals 11/12: is electrically isolated, and is triggered by an active signal.
– Input 2 at terminals 21/22: is not electrically isolated, and is triggered by a passive NO
Requirements
You are familiar with the general procedure described in the section "General information on
installing option modules (Page 48)".
Procedure for installing the alarm module
1. Slide the alarm module into the rack below the basic electronics . Ensure that you slide it
up to the endstop.
2. Connect the module to the basic electronics. For this purpose, use the 8-pin flat ribbon
cable provided.
58
EN 60947-5-6.
35 V.
contact.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12